Energy optimization of air conditioning system using hydrosolar roof as heat sink
Ver/
Compartir
Estadísticas
Ver Estadísticas de usoMetadatos
Mostrar el registro completo del ítemÁrea de conocimiento
Mecánica de FluidosPatrocinadores
The authors wish to acknowledge the collaboration in the calculations of A. Navarro, as well as José María Galán, Energy, Comfort and Enviroment S.L. Manager, as the proporser of the original idea.Fecha de publicación
2006-04Editorial
Elsevier ScienceCita bibliográfica
LUCAS, M., KAISER, A.S., VIEDMA, A. ZAMORA, B. Energy optimization of air conditioning system using hydrosolar roof as heat sink. Solar Energy, 38 (4): 448-458, 2006. ISSN 0038-092XPalabras clave
Tamaño de gotaAire acondicionado
Chimenea solar
Torre de refrigeración
Energía solar
Drop size
Air conditioning
Solar chimney
Cooling tower
Solar energy
Resumen
An environmentally friendly alternative device, called Hydrosolar Roof, designed for heat dissipation in buildings has been necessary to include all the elements in a global model. Then, three main subsystems have been considered: Cooling Machine, Hydraulic Network and Hydrosolar Roof. A description of the three subsystem is done and the mathematical model is presented.The Cooling machine thermodynamic model has been carried out using EES (Engineering Equation Solver). The Hydraulic network model has piping, pump and nozzle information. The Hydrosolar Roof direct contact heat and mass transfer simulation has been development with a CFD code. Special attention has been paid on the cooling efficiency. The global model has been applied to a real prototype facility experimentally tested. All the energy consumptions have been calculated for different pumping heads. A global coefficient of performance (COP) has been defined and the optimum value obtained.