Show simple item record

dc.contributor.authorSánchez Velasco, Francisco Javier 
dc.contributor.authorHaddouche, Mohammed Reda 
dc.contributor.authorIllán Gómez, Fernando 
dc.contributor.authorGarcía Cascales, José Ramón 
dc.date.accessioned2023-02-28T07:25:22Z
dc.date.available2023-02-28T07:25:22Z
dc.date.issued2022-04-18
dc.identifier.citationF.J.S. Velasco, M.R. Haddouche, F. Illán-Gómez, J.R. García-Cascales, Experimental characterization of the coupling and heating performance of a CO2 water-to-water heat pump and a water storage tank for domestic hot water production system, Energy and Buildings, Volume 265, 2022, 112085, ISSN 0378-7788, https://doi.org/10.1016/j.enbuild.2022.112085.es_ES
dc.identifier.issn1872-6178
dc.description.abstractThis work presents an experimental study of the dynamic performance of a CO2 water-to-water heat pump in a domestic hot water production system. A facility was developed and used to characterize the time evolution of the COP of this heat pump, the heating and stratification processes of the hot-water storage tank, and the global COP of the system. Results showed that, when heating the water storage tank, strategies based on promoting stratification to reach Ri ∼40, such as the use of vertical tank filling velocities ∼ 10-4 m·s−1 with low water flow rates between the tank and the heat pump gas cooler, permits an increase of ∼12.4% in the system global COP and a reduction of ∼16% of the compressor energy consumption compared to other strategies. However, strategies based on considering higher water flow rates (i.e. Ri ∼1) increase the thermal energy available in the tank (∼6% when flow rate and increases a factor 3.6) but enhance the water mixing and extend the heating time which reduces the global COP of the system. Besides, an increase of the evaporator inlet water temperature from 5 °C to 20 °C increases the system global COP by 59% and reduces the heating time ∼40%.es_ES
dc.description.sponsorshipThis work has been performed in the context of the project in the project “Maximisation of the efficiency and minimisation of the environmental impact of heap pumps for the decarbonisation of heating and domestic hot water production in nearly zero energy buildings” ENE2017- 83665-C2-2-P, Funded by the Ministry of Economy and Competitiveness, Spain and the support of the European Regional Development Fund. The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.es_ES
dc.formatapplication/pdfes_ES
dc.language.isoenges_ES
dc.publisherELSEVIERes_ES
dc.relation.urihttps://www.sciencedirect.com/science/article/pii/S0378778822002560es_ES
dc.rightsAtribución-NoComercial-SinDerivadas 3.0 España*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/es/*
dc.titleExperimental characterization of the coupling and heating performance of a CO2 water-to-water heat pump and a water storage tank for domestic hot water production systemes_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.subject.otherMecánica de Fluidoses_ES
dc.subjectHeat pumpes_ES
dc.subjectStorage tankes_ES
dc.subjectHot water productiones_ES
dc.subjectCO2es_ES
dc.identifier.urihttp://hdl.handle.net/10317/12129
dc.peerreviewSIes_ES
dc.identifier.doihttps://doi.org/10.1016/j.enbuild.2022.112085
dc.rights.accessRightsinfo:eu-repo/semantics/openAccesses_ES
dc.type.versioninfo:eu-repo/semantics/publishedVersiones_ES
dc.subject.unesco3309.95 Transmisión de Calor en Refrigeración y Calefacciónes_ES
dc.subject.unesco2204.04 Mecánica de Fluidoses_ES
dc.contributor.convenianteUniversidad Politécnica de Cartagenaes_ES


Files in this item

untranslated

This item appears in the following Collection(s)

Show simple item record

Atribución-NoComercial-SinDerivadas 3.0 España
Except where otherwise noted, this item's license is described as Atribución-NoComercial-SinDerivadas 3.0 España