Numerical assessment of the use of a dedicated mechanical subcooling system during hot water generation in a water to water transcritical CO2 heat pump
View/ Open
Identifiers
URI: http://hdl.handle.net/10317/11480ISBN: 978-84-17853-55-6
DOI: 10.31428/10317/11480
Share
Statistics
View Usage StatisticsMetadata
Show full item recordAuthor
Illán Gómez, Fernando; García Cascales, José Ramón; Sánchez Velasco, Francisco Javier; Otón Martínez, Ramón AntonioKnowledge Area
Máquinas y Motores TérmicosSponsors
The authors wish to acknowledge the financial support of the Spanish Ministry of Economy, Industry, and Competitiveness and the European Regional Development Fund through project ENE2017-83665-C2-2-P.Realizado en/con
Universidad Politécnica de CartagenaPublication date
2022Publisher
Universidad Politécnica de Cartagena. Ediciones UPCTBibliographic Citation
ILLÁN GÓMEZ, Fernando et al. Numerical assessment of the use of a dedicated mechanical subcooling system during hot water generation in a water to wáter transcritical CO2 heat pump. En: XI Congreso Ibérico y IX Congreso Iberoamericano de Ciencias y Técnicas del Frío Cytef2022. Avances en Ciencias y Técnicas del Frío - 11. Cartagena: Universidad Politécnica de Cartagena, 2022. Pp. 19-25. ISBN: 978-84-17853-55-6Keywords
CYTEFWater heater
Transcritical cycle
Heat pump
CO2
Abstract
This paper presents a numerical study of the use of a dedicated mechanical subcooling
(DMS) system using R1234yf, for hot water generation in a water-to-water CO2 heat
pump. Compressor mass flow rates and power consumptions were modeled using the manufacturer’s
correlations, expansion valves were modeled as isenthalpic, and heat exchangers
were modeled by deriving correlations for the evaporation/condensation pressure and heat
transfer rate. In the condenser, IMST-ART was used to obtain condensation pressure and heat
transfer rate. A cell-by- cell discretization model was used for the evaporator, which was a
transcritical CO2, subcritical R1234yf heat exchanger. Three different systems were compared
for the transcritical CO2 cycle: with internal heat exchanger (IHX), with DMS, and with
IHX+DMS. Results showed that, for the conditions studied (hot water generation up to 60 ºC
and evaporator water inlet temperature from 5- 25 ºC), the use of a DMS does not improve
the performance ...